NEC 2023

Article 690 Study Guide

Solar Photovoltaic (PV) Systems - National Electrical Code Requirements and Applications

This guide covers NEC Article 690 requirements for safe installation of solar PV systems, including grid-tied, stand-alone, and multimode systems.

⚠️ Code Compliance Notice

This study guide is for educational purposes only. Always refer to the complete, most current edition of the National Electrical Code (NFPA 70) for official requirements. Local jurisdictions may have amendments to the NEC. Always obtain proper permits and inspections for all electrical installations.

Introduction to NEC Article 690

Article 690 of the National Electrical Code provides requirements for the safe installation of electrical equipment, wiring, and components in solar photovoltaic (PV) systems. These requirements apply to all PV systems except those covered under Article 691 (Large-Scale PV Electric Supply Stations).

What is a Solar Photovoltaic System?

A solar PV system converts sunlight into electricity using photovoltaic cells. According to NEC, a PV system includes all components and subsystems that convert solar energy into electrical energy and necessary for system operation, including the interactive components with other energy sources.

Scope and General Requirements

Article 690 applies to PV systems that operate at or below 1000V, though some provisions apply to systems over 1000V. The article covers:

  • PV circuit requirements and calculations
  • Disconnecting means and overcurrent protection
  • Wiring methods and conductor requirements
  • Grounding and bonding
  • Marking and labeling requirements
  • Connection to other sources (grid, generators, etc.)
  • Energy storage systems (covered in Part VII)
  • Stand-alone systems (covered in Part VIII)

I General Requirements (690.1 - 690.15)

690.1 Scope

690.1

Requirement: Article 690 applies to solar PV electrical energy systems including the array circuit(s), inverter(s), and controller(s) for such systems. These systems may be interactive with other electrical power production sources or stand-alone with or without electrical energy storage.

690.2 Definitions

Understanding key definitions is critical for proper application of Article 690:

Term Definition Practical Significance
PV System DC Circuit Any conductors between PV source circuits and the inverter input Different requirements apply to DC vs AC side of system
Interactive System A PV system that operates in parallel with and may deliver power to an electrical production and distribution network Must comply with Article 705 requirements
Rapid Shutdown Reduction of PV system voltage to 80V or less within 30 seconds of shutdown initiation Critical firefighter safety requirement
PV Source Circuit Conductors between modules and from modules to the common connection point of the DC system Calculations for these circuits differ from other circuits

690.4 General Requirements

690.4

Requirement: PV systems shall be permitted to supply a building or other structure in addition to any other electricity supply systems. All equipment must be listed and identified for PV system use.

Practical Application:

When installing a PV system, ensure all components (inverters, combiners, disconnects) are specifically listed for solar PV applications. Using equipment not listed for PV use violates 690.4 even if the equipment is listed for general electrical use.

690.7 Maximum Voltage

690.7

Requirement: The maximum PV system voltage is the highest voltage between any two conductors of the PV system. For modules rated 1000V or less, calculate using the lowest expected ambient temperature.

Voltage Calculation Steps

1. Determine module open-circuit voltage (Voc) from manufacturer specifications
2. Determine temperature correction factor for coldest expected temperature (NEC Table 690.7)
3. Multiply Voc by temperature correction factor
4. For series connections, multiply by number of modules in series
5. This gives maximum system voltage for component rating selection

2023 Code Change Highlight:

690.7(C) Increased Voltage Limits: For dwelling units, the maximum voltage for PV systems is now permitted to be 1000V (increased from 600V) when the installation complies with all requirements for 1000V systems.

II Circuit Requirements (690.8 - 690.9)

690.8 Circuit Sizing and Current

690.8

Requirement: The maximum current for PV circuits is calculated as 125% of the short-circuit current (Isc) marked on the module. For continuous current conditions, additional 125% factor applies.

Current Calculation Example:

If a PV module has Isc = 10A:
1. Maximum circuit current = 10A × 1.25 = 12.5A
2. For continuous operation (3+ hours) = 12.5A × 1.25 = 15.625A
3. Conductor ampacity must be at least 15.625A
4. Overcurrent device must be rated at least 15.625A (next standard size up)

690.8(A) Sizing of Module Interconnection Conductors

When connecting modules in parallel, the conductors between modules and to the common connection point must be sized at least 125% of the module short-circuit current.

690.8(B) Conductor Ampacity

PV system conductors must have ampacity not less than 125% of the maximum currents calculated in 690.8(A). Adjustments for conditions of use (temperature, conduit fill) apply per NEC 310.15.

690.9 Overcurrent Protection

690.9

Requirement: PV system DC circuits must be protected against overcurrent. There are exceptions for certain conductor sizes and configurations. Overcurrent devices must be listed for DC operation and PV use.

Circuit Type Overcurrent Protection Required? Common Exception
Single series string Generally not required 690.9(A) Exception: If conductors sized per 690.8(B)
Multiple parallel strings Required for each string Protection required at point of parallel connection
Battery circuits Always required Must be accessible and within battery enclosure
AC inverter output Required per Article 705 Standard AC circuit breaker typically used

III Disconnecting Means (690.13 - 690.15)

690.13 Photovoltaic System Disconnecting Means

690.13

Requirement: Means shall be provided to disconnect all current-carrying conductors of a PV system from all other conductors in a building. The disconnecting means must be externally operable, indicate open/closed position, and be rated for the maximum circuit voltage and current.

Critical Safety Requirement:

PV system disconnects must be installed at readily accessible locations. For one- and two-family dwellings, the disconnect must be installed at a location normally accessible to first responders (not on the roof). This supports rapid shutdown requirements.

690.13(B) Type of Disconnect

The PV system disconnecting means shall be one of the following:

  • A manually operable switch or circuit breaker
  • A connector meeting specific requirements
  • A pull-out type switch or connector
  • Other approved means

690.13(C) Ratings

The disconnecting means must have a rating not less than 115% of the maximum circuits current calculated per 690.8.

690.12 Rapid Shutdown of PV Systems

690.12

Requirement: PV systems on buildings shall have rapid shutdown to reduce shock hazard for emergency responders. Within 30 seconds of initiation, voltage must be reduced to 80V or less on the roof and to 30V or less within 1 ft of the array boundary.

2023 Code Change Highlight:

690.12(B)(2) Expanded Rapid Shutdown: Rapid shutdown initiation now includes activation by a readily accessible switch at the service disconnecting means OR automatic shutdown upon loss of utility power for interactive systems.

Implementing Rapid Shutdown

1. Install rapid shutdown initiation switch at service disconnect location
2. Use listed rapid shutdown equipment (modules, inverters, combiners)
3. Ensure equipment reduces voltage to required levels within 30 seconds
4. Label all rapid shutdown equipment and initiation points clearly
5. Include rapid shutdown information in plans submitted for permit

IV Wiring Methods (690.31 - 690.34)

690.31 Wiring Methods

690.31

Requirement: PV system wiring shall be installed in accordance with the applicable provisions of Article 300 and other relevant articles. Specific wiring methods are prescribed for different locations within the PV system.

690.31(A) Wiring Systems

Permitted wiring methods for PV circuits include:

Location Permitted Wiring Methods Special Requirements
Module interconnection Listed PV wire, USE-2, or other approved cables Must be sunlight resistant if exposed
Within buildings Raceways (conduit) with THWN-2, XHHW-2, or PV wire DC conductors in metal raceway must have insulation rated for circuit voltage
Outdoor locations PVC, RMC, IMC, EMT, or listed outdoor cables Must be suitable for wet locations
Roof penetrations Raceways with listed flashing or sealed penetrations Must maintain weatherproof integrity of roof

690.31(B) Single-Conductor Cable

Single-conductor Type PV wire or USE-2 cables are permitted for module interconnections and within array. They must be installed in accordance with specific securing and protection requirements.

690.31(C) Multiconductor Cable

Multiconductor cables are permitted for interconnection of array components. When installed as exposed wiring, cables must be secured at intervals not exceeding 24 inches.

690.31(E) DC PV Circuits in Buildings

Important Restriction:

DC PV circuits inside buildings must be contained in metal raceway, metal enclosures, or consist of MC cable. Exceptions exist for PV circuits run inside the array boundary or for DC circuits from building-integrated PV modules.

690.33 Connectors

690.33

Requirement: Connectors for PV systems must be polarized, require a tool to open, be listed for the application, and be of the latching or locking type. Mismatable connectors (different keying) must be used for different electrical systems.

V Grounding and Bonding (690.41 - 690.47)

690.41 System Grounding

690.41

Requirement: PV systems shall be grounded in accordance with Article 250. For PV systems, either functional grounding (for system operation) or equipment grounding (for safety) may be required.

690.41(A) Systems Over 50V

PV systems with maximum system voltages over 50V must have one conductor grounded or have a functional ground. Functional grounding means a grounded system where the grounding is needed for proper system operation.

690.41(B) Systems 50V or Less

PV systems with maximum system voltages of 50V or less are not required to be grounded. However, equipment grounding is still required for safety.

690.42 Point of System Grounding Connection

The DC system grounding connection shall be made at any single point on the PV output circuit. This is typically done in the inverter or a dedicated DC grounding device.

690.43 Equipment Grounding

690.43

Requirement: Exposed non-current-carrying metal parts of PV system equipment shall be grounded in accordance with Article 250, regardless of voltage.

Equipment Grounding Requirements:

All metal parts including module frames, racking, enclosures, and conduit must be bonded together and connected to the grounding electrode system. Equipment grounding conductors must be sized per NEC Table 250.122 based on overcurrent device rating.

690.45 Size of Equipment Grounding Conductors

Equipment grounding conductors for PV source and output circuits shall be sized per 250.122 but not smaller than 14 AWG. For PV arrays, additional requirements apply for grounding conductor sizing.

690.47 Grounding Electrode System

PV systems shall be connected to a grounding electrode system per 250.50. Where separate electrodes are used, they must be bonded together per 250.58.

Appendix: Quick Reference Tables & Checklists

PV System Installation Checklist

Pre-Installation

□ Review manufacturer installation instructions for all components
□ Calculate maximum system voltage (690.7)
□ Calculate maximum circuit currents (690.8)
□ Size conductors and overcurrent protection (690.8, 690.9)
□ Determine grounding requirements (690.41-47)
□ Plan rapid shutdown implementation (690.12)

Installation

□ Install proper wiring methods (690.31)
□ Ground all equipment (690.43)
□ Install disconnects in accessible locations (690.13)
□ Install rapid shutdown equipment (690.12)
□ Use proper connectors (690.33)
□ Bond all metal parts (690.43)

Post-Installation

□ Apply required labels (690.53-56)
□ Test system operation
□ Verify rapid shutdown function
□ Document system for inspector
□ Provide owner with operation manual

Common NEC References for PV Systems

Requirement Primary NEC Article Key Sections
General electrical requirements Article 110 110.3(B), 110.14, 110.26
Grounding and bonding Article 250 250.4, 250.50, 250.122
Overcurrent protection Article 240 240.4, 240.6, 240.21
Wiring methods Article 300 300.3, 300.4, 300.5
Connection to utility Article 705 705.12, 705.20, 705.30
Battery systems Article 480 480.7, 480.9, 480.10

Required PV System Labels (690.53-56)

Mandatory Labeling Requirements:

690.53 - DC PV Power Source: "WARNING: ELECTRIC SHOCK HAZARD - DO NOT TOUCH TERMINALS - TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION"

690.54 - Interactive System Point of Interconnection
690.55 - Photovoltaic Power Source (AC disconnect)
690.56 - Rapid Shutdown (type and location of initiation)

Labels must be durable, permanently affixed, and visible after installation.

Final Reminder:

This study guide summarizes key requirements of NEC Article 690 but is not a substitute for the complete code. Always consult the latest edition of NFPA 70 National Electrical Code for complete requirements. Local jurisdictions may have amendments. When in doubt, consult with a licensed electrical professional or local authority having jurisdiction (AHJ).